Specialty coolants

LM-17 series

Dielectric immersion cooling fluids

A dedicated immersion-cooling range for data-centre server systems, developed around electrical insulation, thermal and oxidative stability and yellowing resistance. The catalogue states the fluids contain no corrosive sulfur.

GLACIER / PRODUCT SAMPLELM-17 series product photograph
Manufacturer product photograph.
CATALOGUE TEMPERATURE REFERENCELM-17A: 0 to +100°C · LM-17B: −5 to +100°C · LM-17C: −30 to +100°C (product list, April 2026)
Formulation

Modified hydrocarbons

A closer look.

  • Server immersion cooling
  • Electrical-insulation properties
  • Thermal and oxidative stability focus
  • Breakdown voltage as stated in the catalogue

Model and property references

LM-17A operating range
0 to +100°C
LM-17B operating range
−5 to +100°C
LM-17C operating range
−30 to +100°C
LM-17A breakdown voltage
65.6 kV, catalogue reference
LM-17B breakdown voltage
74.5 kV, catalogue reference
LM-17C breakdown voltage
84.3 kV, catalogue reference
LM-17C viscosity at 20°C
3.42 cP

LM-17 series catalogue reference values (Table 15)

ModelPour point (°C)Viscosity (cP)Density (g/cm³)Specific heat (cal/g·°C)Thermal conductivity (W/m·K)Flash point (°C)Breakdown voltage (kV)
LM-17A≤−5021.130.8890.429 cal/(g·°C) = 1.79 kJ/(kg·K)0.11213665.6
LM-17B≤−4714.970.8840.424 cal/(g·°C) = 1.77 kJ/(kg·K)0.109138.574.5
LM-17C≤−403.420.8480.427 cal/(g·°C) = 1.79 kJ/(kg·K)0.11210784.3

All properties are printed at 20°C. The operating range for each model is listed above.

LM-17A–C immersion properties (mfr. BESS liquid-cooling document)

PropertyLM-17ALM-17BLM-17C
Base fluidHydrocarbonHydrocarbonHydrocarbon
Pour point (°C)−50−47−40
Electrical conductivity (µS/cm)000
Compatible metalsCarbon steel, copper, aluminium, stainless steel
FlammabilityNon-flammableNon-flammableNon-flammable
ApplicationImmersion cooling, non-phase-change heat transfer
Flash point per catalogue (°C)136138.5107

From the manufacturer's BESS liquid-cooling document. It states these fluids as non-flammable; the catalogue prints a flash point for each model.

Reference values from the Chaoyang Guangda LM catalogue — typical figures rather than guaranteed limits. Confirm the exact model and concentration on the current model TDS before specifying.

View source: catalogue p.28 (PDF p.32)

Before you specify

Operating ranges are from the manufacturer's product list, April 2026. Confirm electrical test methods, equipment approvals and compatibility with every wetted material for the model you specify.

THE RIGHT FLUID STARTS WITH A CONVERSATION

Your process is specific.
Your coolant should be, too.

Share your temperatures, materials and application.
Let’s work through the right formulation together.

Discuss your application