LABORATORY DATA

Measured,
not asserted.

Third-party corrosion, flash point and hazard classification results for the LM fluids.
Each table names the laboratory, the report number and the standard behind it.

What these figures cover

Four reports, commissioned by the manufacturer and issued by accredited laboratories, covering uniform corrosion of three metals and the flammability classification of LM-4. The sample, concentration and test conditions are stated with each result because corrosion and flash point both move with concentration.

A test result describes the sample and conditions in the report. Applying it to your loop starts from the model, the dilution and the wetted materials in your system.

CORROSION

Three metals, two fluids,
one reference rate.

The reference rate is the limit in GB/T 50050-2017 for industrial recirculating cooling water. Measured rates sit 180 to 280 times below it on stainless steel and copper, and about 230 times below it on carbon steel.

Corrosion rates of Q235 carbon steel, 304 stainless steel and T2 red copper in LM-4 and LM-8, against the GB/T 50050-2017 reference rate, on a logarithmic scale.
Measured in millimetres per year on a logarithmic axis. A logarithmic scale is used because the three metals differ in corrosion resistance by more than a factor of ten.
How many times lower the LM-4 and LM-8 corrosion rates are than the GB/T 50050-2017 reference rate for each of the three metals.
The same measurements expressed as a ratio to the reference rate. LM-8 is the higher-carbon-steel performer and the lower-copper performer; both clear the reference rate on all three metals.
Uniform corrosion rate, immersion at 30 °C for 174 h (mm/a)
MetalGB/T 50050-2017 referenceLM-4LM-8LM-4 vs referenceLM-8 vs reference
Q235 carbon steel0.0753.32×10⁻⁴3.16×10⁻⁴226× lower237× lower
304 stainless steel0.0051.97×10⁻⁵2.78×10⁻⁵254× lower180× lower
T2 red copper0.0051.8×10⁻⁵8.98×10⁻⁵278× lower56× lower

The report records no macroscopic corrosion on any of the three metals in either fluid, within the 174-hour test window. Copper in LM-8 measures 8.98 × 10⁻⁵ mm/a against 1.80 × 10⁻⁵ mm/a in LM-4 — both far below the reference rate, and the one place where the two fluids separate.

REPORTS

The four reports
behind the tables.

Corrosivity of LM-4 and LM-8 on carbon steel, stainless steel and red copper

REPORT 01
Sample
LM-4 and LM-8
Laboratory
Institute of Metal Research, Chinese Academy of Sciences
Report number
金LPCS-2019-10-001
Report date
17 October 2019
Standard
JB/T 7901-1999 — uniform corrosion, laboratory immersion testing · GB/T 50050-2017 — industrial recirculating cooling water treatment
  • Immersion at 30 °C, 174 hours, on Q235 carbon steel, 304 stainless steel and T2 red copper.
  • Mean corrosion rate in LM-8: 3.16 × 10⁻⁴, 2.78 × 10⁻⁵ and 8.98 × 10⁻⁵ mm/a respectively.
  • Mean corrosion rate in LM-4: 3.32 × 10⁻⁴, 1.97 × 10⁻⁵ and 1.80 × 10⁻⁵ mm/a respectively.
  • The report records no macroscopic corrosion on any of the three metals in either fluid.

Open-cup flash point identification for LM-4 (75 %)

REPORT 02
Sample
LM-4 at 75 %
Laboratory
Shenyang Product Quality Supervision and Inspection Institute · CMA, CAL, ilac-MRA, CNAS
Report number
2019501WSHX01470
Report date
29 September 2019
Standard
GB/T 3536-2008 — flash point determination, open-cup method
  • Test item: open-cup flash point.
  • Result recorded as no flash point.

Chemical physical hazard identification for LM-4

REPORT 03
Sample
LM-4
Laboratory
Chemical Registration Centre, Ministry of Emergency Management
Report number
G20190702A001
Report date
8 July 2019
Standard
GB 30000.7-2013 — classification and labelling of chemicals, flammable liquids · GB/T 5208-2008 — flash point determination, rapid equilibrium closed-cup method
  • Closed-cup flash point: no flash at 93 °C.
  • pH: 8.21.
  • Classification under GB 30000.7-2013: not a flammable liquid.

Fire classification for LM-4 (55 %)

REPORT 04
Sample
LM-4 at 55 %
Laboratory
Quality Supervision and Inspection Center for Synthetic Material Aging, Chemical Industry · CMA, CNAS, ilac-MRA
Report number
W2005003181
Report date
9 May 2020
Standard
GB 30000.1-2013 — classification and labelling of chemicals
  • Closed-cup flash point above 100 °C; classified as not a flammable liquid.
  • Screened against sixteen hazard classes; the classifications are listed in the table below.

HAZARD CLASSIFICATION

Sixteen classes,
screened for LM-4 at 55 %.

GB 30000.1-2013 sets out sixteen physical hazard classes. Each was assessed for the sample and the classification recorded.

No.Hazard classClassification
1ExplosivesNot an explosive
2Flammable gasesNot applicable
3AerosolsNot applicable
4Oxidising gasesNot applicable
5Gases under pressureNot applicable
6Flammable liquidsNot a flammable liquid
7Flammable solidsNot applicable
8Self-reactive substances and mixturesNot self-reactive
9Pyrophoric liquidsNot pyrophoric
10Pyrophoric solidsNot applicable
11Self-heating substances and mixturesNot applicable
12Substances which, in contact with water, emit flammable gasesDoes not emit flammable gases in contact with water
13Oxidising liquidsNot an oxidising liquid
14Oxidising solidsNot applicable
15Organic peroxidesNot an organic peroxide
16Corrosive to metalsNot corrosive to metals

Classification applies to the sample at 55 % as tested. Flash point and flammability classification move with concentration, so a different dilution is classified on its own report. The SDS for the model and concentration in use carries the classification that governs handling and transport.

USING THESE RESULTS

From a test coupon
to a system decision.